Prekių katalogas

G One, 1 kilpos adresuojama gaisro centralė

  • G One, 1 kilpos adresuojama gaisro centralė

    Kodas: 01029
  • MAINS POWER SUPPLY RATING 90V AC to 230V AC
    PRIMARY DC SUPPLY 28.5V DC @ 2.4 A (Max)
    SECONDARY SUPPLY 21.6 Min. - 27.2V DC (Max) - Battery charger: 27.5V DC
    BATTERY CAPACITY (INTERNA) 2 x 12V 9AH SLA
    QUIESCENT CURRENT (NO DEVICES) 55 mA
    AUX POWER OUTPUT 2 x 24V DC 300mA / 1 x 24V switched output
    MAXIMUM LOOP OUTPUT CURRENT 1 loop - 900mA alarm peak/165mA quiescent
    LOOP TOPOLOGY Class A (loop) or Class B (radial)
    LOOP CABLE Fire resistant 2 x 1.5mm (max 1200m) or 2 x 2.5mm (max 2000m)
    CONVENTIONAL SOUNDER CIRCUITS 2 x 500 mA Max current drive for both circuits - Fully monitored
    AUX. RELAYS FIRE 2 x rated 2A @ 30V DC resistive / 0.5A @ 120V AC resistive/ 0.25A @ 240V AC resistive
    AUX. RELAY FAULT 1 rated 2A @ 30V DC resistive / 0.5A @ 120V AC resistive/ 0.25A @ 240V AC resistive
    GRAPHICAL LCD DISPLAY High definition, high contrast blue backlit 240 x 64 pixels
    COMMUNICATION CHANNELS 2 x configurable communication ports
    BMS OUTPUT ODYSSEY (Graphical software), TCP IP-WEB (remote web monitoring), MODBUS RTU, ESPA 4.4.4
    SOFTWARE CONNECTION USB type B
    EVENT LOG 10,000 events
    OPERATING / STORAGE TEMPERATURE -10?C to 50?C
    HUMIDITY Max. 85% RH Non-Condensing
    INGRESS PROTECTION Surface Mount: IP30, Recessed Mount: IP65
    DIMENSIONS 273 (L) x 404 (H) x 107 (W) mm
    WEIGHT 1.6 KG (no batteries)
    ENCLOSURE COLOURS White (RAL 9003) or Red (RAL 3001)